Click or drag to resize
Grid Solutions Framework

StatusFlags Enumeration

eDNA point status flags.

Namespace: eDNAAdapters
Assembly: eDNAAdapters (in eDNAAdapters.dll) Version: 2.4.218-beta
Syntax
[FlagsAttribute]
public enum StatusFlags
View Source
Members
Member nameValueDescription
RTSTAT_UNUSED0 Not yet initialized.
RTSTAT_INITED1 Has been initialized.
RTSTAT_UPDATED2 Has been updated.
ANALOG_OK3 Analog Point Initialized, Received Value, Reliable Quality.
RTSTAT_UNRELIABLE4 Data is bad.
ANALOG_UNRELIABLE7 Analog Point Initialized, Received Value, Unreliable Quality,
RTSTAT_OOR8 Sensor bad.
EVAL-1 Evaluate status.
RTSTAT_LL_ALARM16 Low-low alarm.
RTSTAT_L_ALARM32 Low alarm.
ANALOG_LOW_WARNING35 Analog Point Initialized, Received Value, Reliable Quality, Value goes below Low Warning Threshold.
ANALOG_LOW_ALARM51 Analog Point Initialized, Received Value, Reliable Quality, Value goes below Low Alarm Threshold.
ANALOG_LOW_OUT_OF_RANGE59 Analog Point Initialized, Received Value, Reliable Quality, Value goes below Low Out of Range Threshold.
RTSTAT_H_ALARM64 High alarm.
ANALOG_HIGH_WARNING67 Analog Point Initialized, Received Value, Reliable Quality, Value goes above High Warning Threshold.
RTSTAT_HH_ALARM128 High-high alarm.
ANALOG_HIGH_ALARM195 Analog Point Initialized, Received Value, Reliable Quality, Value goes above High Alarm Threshold.
ANALOG_HIGH_OUT_OF_RANGE203 Analog Point Initialized, Received Value, Reliable Quality, Value goes above High Out of Range Threshold.
RTSTAT_MANUAL256 Manual input.
ANALOG_OK_MANUAL259 Analog Point Initialized, Received Value, Manually Input into eDNA, Reliable Quality.
ANALOG_UNRELIABLE_MANUAL263 Analog Point Initialized, Received Value, Manually Input into eDNA, Unreliable Quality.
RTSTAT_UNACKRST512 Reset not acknowledged.
ANALOG_OK_UNACK_ALARM515 Analog Point Initialized, Received Value, Reliable Quality, Reset Unacknowledged Alarm.
RTSTAT_UNACKAL1,024 Alarm not acknowledged.
ANALOG_LOW_WARNING_UNACK_ALARM1,059 Analog Point Initialized, Received Value, Reliable Quality, Value goes below Low Warning Threshold, Unacknowledged Alarm.
ANALOG_LOW_ALARM_UNACK_ALARM1,075 Analog Point Initialized, Received Value, Reliable Quality, Value goes below Low Alarm Threshold, Unacknowledged Alarm.
ANALOG_LOW_OUT_OF_RANGE_UNACK_ALARM1,083 Analog Point Initialized, Received Value, Reliable Quality, Value goes below Low Out of Range Threshold, Unacknowledged Alarm.
ANALOG_HIGH_WARNING_UNACK_ALARM1,091 Analog Point Initialized, Received Value, Reliable Quality, Value goes above High Warning Threshold, Unacknowledged Alarm.
ANALOG_HIGH_ALARM_UNACK_ALARM1,219 Analog Point Initialized, Received Value, Reliable Quality, Value goes above High Alarm Threshold, Unacknowledged Alarm.
ANALOG_HIGH_OUT_OF_RANGE_UNACK_ALARM1,227 Analog Point Initialized, Received Value, Reliable Quality, Value goes above High Out of Range Threshold, Unacknowledged Alarm.
RTSTAT_REPEAT2,048 Tickle flags for history repeat.
ANALOG_OK_FORCED2,051 Analog Point Initialized, Received Value, Reliable Quality, Repeat History Value (Forced).
RTSTAT_DIGITAL_IN4,096 Digital point type.
DIGITAL_NOT_UPDATED4,097 Digital Point Initialized, not received a value.
DIGITAL_OK_NOT_SET4,099 Digital Point Initialized, Received Value, Reliable Quality, Value = 0.
DIGITAL_UNRELIABLE_NOT_SET4,103 Digital Point Initialized, Received Value, Unreliable Quality, Value = 0.
DIGITAL_CHATTERING_NOT_SET4,115 Digital Point Initialized, Received Value, Reliable Quality, Value = 0, Chattering Flag Set.
DIGITAL_OK_SET4,163 Digital Point Initialized, Received Value, Reliable Quality, Value = 1.
DIGITAL_UNRELIABLE_SET4,167 Digital Point Initialized, Received Value, Unreliable Quality, Value = 1.
DIGITAL_CHATTERING_SET4,179 Digital Point Initialized, Received Value, Reliable Quality, Value = 1, Chattering Flag Set.
DIGITAL_WARNING_NOT_SET4,227 Digital Point Initialized, Received Value, Reliable Quality, Value = 0, Warning Flag Set.
DIGITAL_WARNING_SET4,291 Digital Point Initialized, Received Value, Reliable Quality, Value = 1, Warning Flag Set.
DIGITAL_OK_NOT_SET_FORCED6,147 Digital Point Initialized, Received Value, Reliable Quality, Value = 0, Repeat History Value (Forced).
DIGITAL_OK_SET_FORCED6,211 Digital Point Initialized, Received Value, Reliable Quality, Value = 1, Repeat History Value (Forced).
RTSTAT_ANALOG_OUT8,192 Analog point type.
RTSTAT_DIGITAL_OUT12,288 Digital point type.
See Also